Final | 1/5/2007 | 1/8/2007 | 1/8/2007 | P | CANC |
Jack Frank
|
|
|
mason; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
Electrical Rough-In | 1/8/2007 | 1/8/2007 | 1/8/2007 | P | PASS |
Jack Frank
|
|
|
mason; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok owner needs to install 18 cu.in. for ceiling recepts east end 3 boxes
|
Final | 12/12/2006 | 12/13/2006 | 12/13/2006 | P | CANC |
Jack Frank
|
|
|
mason ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith Inspection cancelled from web by: Cathy Weisshaupt
|
Electrical Rough-In | 11/17/2006 | 11/21/2006 | 11/21/2006 | P | FAIL |
Jack Frank
|
|
|
mason; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. met owner, 210.52(A) outlet spacing north wall, 300.14 6"free length, 110.26 subpanel shall be flush with finish for clearence, 314.43 no sscrews in plastic boxes, 210.70(A)(2)(b)light for exit door switch or automatic mean to turn off or on, 250.24(A)(5) isolate grds and neuts at subpanel, 250.148 grd metal boxes, 314.20 all boxes flush with wood finish, 314.27 needs listed fan boxes, 404.9 grd pigtail for all switches
|
Application received | | | 4/21/2006 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 4/21/2006 | | DONE |
|
|
|
|