Temporary Service | 4/25/2006 | 4/25/2006 | 4/25/2006 | P | PASS |
Bob Reichert
|
|
|
###-#### -rick corr made, t/s u/g n ok
|
Temporary Service | 4/24/2006 | 4/24/2006 | 4/24/2006 | P | FAIL |
Bob Reichert
|
|
|
###-#### - rick called contr, left message, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 408.4 circuit directory shall be provided, 110.14(A) grounding electrode connection to terminal at rod shall ensure a thoroughly good connection, fee due
|
Issue permit | | | 4/24/2006 | | |
|
|
|
|
Application received | | | 4/24/2006 | | |
|
|
|
|
Stop Work/Reinspection Fee | 4/24/2006 | 4/24/2006 | | P | |
Bob Reichert
|
|
|
see notes for t/s
|