Permit NumberELE06-01398
StatusFinaled
Name RICKS ELECTRIC SERVICE
Site Address 2452 N PENNY ROYAL AVE
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Temporary Service4/25/20064/25/20064/25/2006PPASS
DetailsBob Reichert
###-#### -rick corr made, t/s u/g n ok
Temporary Service4/24/20064/24/20064/24/2006PFAIL
DetailsBob Reichert
###-#### - rick called contr, left message, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 408.4 circuit directory shall be provided, 110.14(A) grounding electrode connection to terminal at rod shall ensure a thoroughly good connection, fee due
Issue permit  4/24/2006  
Application received  4/24/2006  
Stop Work/Reinspection Fee4/24/20064/24/2006 P 
DetailsBob Reichert
see notes for t/s