Final | 6/15/2006 | 6/16/2006 | 6/16/2006 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 6/15/2006 at 4:19:45 PM. Contact: ###-####. corr made, ok to final
|
Final | 6/13/2006 | 6/13/2006 | 6/13/2006 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 6/13/2006 at 7:35:31 AM. Contact: ###-####. called, left corr notice, nec 408.4 every circuit shall be identified to its clear, evident and specific purpose, 406.5 cover plates shall seat against mounting surface, 406.4(D) recpt faces shall be flush with or project from faceplates, 440.4(A) a/c shall be provided wirh nameplate, 422.31(B) dishwasher shall have lock-out provisions,BCC disposal shall be wired
|
Rough-In Permanent Service | 4/27/2006 | 5/1/2006 | 5/1/2006 | A | PASS |
Bob Reichert
|
|
|
###-#### ric ok, p/s u/g n ok
|
Issue permit | | | 4/27/2006 | | DONE |
|
|
|
|
Application received | | | 4/27/2006 | | |
|
|
|
|