Temporary Service | 5/1/2006 | 5/1/2006 | 5/1/2006 | P | PASS |
Bob Reichert
|
|
|
###-#### or ###-#### corr made t/s u/g n ok
|
Temporary Service | 4/28/2006 | 4/28/2006 | 4/28/2006 | P | FAIL |
Bob Reichert
|
|
|
ted- ###-#### t/p called contr, left corr notice, 312.5 all conductors entering enclosures shall have abrasion protection, 310.7 conductors used for dierct burial shall be of a type identified for such use, 250.20 gec shall be connected, 250.24(A) gec shall be connected to grounded conductor terminal, BCC job id sticker shall be posted
|
Issue & PRINT permit | | | 4/28/2006 | | DONE |
|
|
|
|
Application received | | | 4/28/2006 | | |
|
|
|
|