Final | 7/21/2006 | 7/21/2006 | 7/21/2006 | A | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: joe wheeler ok final
|
Rough-In Permanent Service | 5/10/2006 | 5/11/2006 | 5/11/2006 | A | PART |
Pat Lass
|
|
|
callfor access house may be locked; Phone #: ###-#### Internet Inspection Request from: joe wheeler guy is to be within 30 in of weatherhead and use plastic romex connectors on GEC R/I Ok
|
Rough-In Permanent Service | 5/10/2006 | 5/10/2006 | 5/10/2006 | A | FAIL |
Jack Frank
|
|
|
call for access; Phone #: ###-#### Internet Inspection Request from: joe wheeler corr. 312.5 needs conn. for GEC,310.8(D) sunlight resistant wire for mast 230.54(C) wheaterhead shall be above service drop atachment as code noted states, 230.24(B)(1) needs 10ft from grade to drip loop,250.148 shall have all metal boxes grded at time of r/i request, 314.16 box fill outside back recept, 314.17(A&B) needs conn or clamps at all metal boxes
|
Application received | | | 5/1/2006 | | DONE |
|
|
|
This permit was created on the web by joe wheeler
|