Temporary Service | 5/18/2006 | 5/19/2006 | 5/19/2006 | A | PASS |
Mike Kinnear
|
|
|
george; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa t/s o/h n ok
|
Stop Work/Reinspection Fee | 5/4/2006 | 5/4/2006 | 5/18/2006 | P | DONE |
Mike Kinnear
|
|
|
George; Phone #: ###-#### Internet Inspection Request from: Ione Coleman to many corrections see other inspection.
|
Temporary Service | 5/3/2006 | 5/4/2006 | 5/4/2006 | P | FAIL |
Mike Kinnear
|
|
|
George; Phone #: ###-#### Internet Inspection Request from: Ione Coleman coreections NEC250.53(G) ground rod 8ft in the ground & ground wire shall be installed with plastic romex connector NEC406.8(B) all weather proof covers shall be inuse style covers. NEC406.6 all cord outlets shall be listed & marked with the manufactures name or identification & voltage & ampere ratings (note thirty amp breaker can not be on twenty amp. outlet.) (240 volt) called numberous times phone busy. note reinspection fee due.
|
Application received | | | 5/3/2006 | | |
|
|
|
|
Issue permit | | | 5/3/2006 | | DONE |
|
|
|
|