Final | 2/9/2007 | 2/9/2007 | 2/9/2007 | P | PASS |
William E Thomas
|
|
|
Can you call a hour roughly before so I can get to the residence and make sure we have access. thank you. Robert Phone #: ###-#### 1. final ok-- survey note -- 210.52 recep space
|
Final | 8/21/2006 | 8/21/2006 | 8/21/2006 | P | CANC |
Jack Frank
|
|
|
Terry; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called elect. contr. owner did work on his permit and called for final job all messed up, contr. will talk with owner and finish trim out of kit. and correct all wiring
|
Permanent Service | 6/8/2006 | 6/8/2006 | 6/8/2006 | P | PASS |
Jack Frank
|
|
|
Might call before to gain access.; Phone #: ###-#### Internet Inspection Request from: Robert Murray p/s o/h rec. ok
|
Electrical Rough-In | 5/9/2006 | 5/9/2006 | 5/9/2006 | A | PASS |
Jack Frank
|
|
|
might call again to set up time for access.; Phone #: ###-#### Internet Inspection Request from: Robert Murray ok
|
Electrical Rough-In | 5/8/2006 | 5/8/2006 | 5/8/2006 | P | FAIL |
Jack Frank
|
|
|
Can you call me about an hour before due to I have the access into the house. Thank you; Phone #: ###-#### Internet Inspection Request from: Robert Murray corr. met contr. 314.43 no screws in plastic boxes, 314.16 box fill, 334.30/314.17(C) staple romex 8" of boxes, 300.4(A)(1)&(D) nail plates and 11/4", 210.52(B) no lights on SABC
|
Application received | | | 5/5/2006 | | DONE |
|
|
|
This permit was created on the web by Robert Murray
|