Second Notice ELE | 6/7/2006 | 6/7/2006 | 6/16/2006 | | DONE |
|
|
|
This permit finaled on the web by Celinda Winters
|
First Notice | 5/17/2006 | 5/17/2006 | 6/7/2006 | | DONE |
Jack Frank
|
|
|
|
Permanent Service | 5/16/2006 | 5/17/2006 | 5/17/2006 | A | PASS |
Jack Frank
|
|
|
Suite 110 - reinspection ; Phone #: ###-#### Internet Inspection Request from: Celinda Winters p/s o/h rec. for meter
|
Final | 5/17/2006 | 5/17/2006 | 5/17/2006 | A | PASS |
Jack Frank
|
|
|
Suite 110 - reinspection ; Phone #: ###-#### Internet Inspection Request from: Celinda Winters
|
Permanent Service | 5/15/2006 | 5/16/2006 | 5/16/2006 | A | FAIL |
Jack Frank
|
|
|
###-#### - celica winters corr. called 250.28 where is the bond screw?, 250.66&28(D) shall use #4 copper too all bond bushings for line side, 408.3(E) high leg shall be B phase
|
Owner Supplied Equipment | | | 5/10/2006 | | |
|
|
|
|
Application received | | | 5/10/2006 | | DONE |
|
|
|
This permit was created on the web by Celinda Winters
|