Final | 8/28/2006 | 8/28/2006 | 8/28/2006 | P | PASS |
Bob Reichert
|
|
|
front door lock box 4718; Phone #: ###-#### Internet Inspection Request from: Todd Holbrook ok to final
|
Final | 8/10/2006 | 8/10/2006 | 8/10/2006 | P | FAIL |
Bob Reichert
|
|
|
garage code 1234 lock box on front door code is 4718; Phone #: ###-#### Internet Inspection Request from: Todd Holbrook called left corr notice, nec 110.26(F)(1)&(2) there shall be no foreign systems in dedicated electrical space(panel and meter) (clearance shall be maintained), 406.4(D) after installation, recpt faces shall be flush with or project from faceplates, 404.9(A) switch faceplates shall seat against finished surface
|
Rough-In Permanent Service | 5/15/2006 | 5/15/2006 | 5/15/2006 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook corr made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 5/14/2006 | 5/15/2006 | 5/15/2006 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook called contr, left corr notice, nec 334.30 nm cable shall be stapled within 12" of enclosure, 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members, 210.52(A)(1) wall space over 6' shall have recpt, BCC all make-up shall be done,a/c disc set
|
Application received | | | 5/12/2006 | | DONE |
|
|
|
This permit was created on the web by Todd Holbrook
|