Final | 6/1/2006 | 6/1/2006 | 6/1/2006 | P | PASS |
William E Thomas
|
|
|
this is for the service only, we were unable to get co-operation from the owner for the interior.
|
Permanent Service | 6/1/2006 | 6/1/2006 | 6/1/2006 | P | PASS |
William E Thomas
|
|
|
p/s o/h reconnect ok
|
Final | 5/30/2006 | 5/30/2006 | 5/30/2006 | P | FAIL |
Jack Frank
|
|
|
Ron; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt grd rods not 6ft apart he drove the 2nd rod at 45 degrees towards the other grd rod, owner told me the get off his property so I left called Jim S
|
Permanent Service | 5/22/2006 | 5/23/2006 | 5/23/2006 | A | FAIL |
William E Thomas
|
|
|
runyon; Phone #: ###-#### Internet Inspection Request from: Darla Downs 1. needs two ground rods 2. needs to ground the water system
|
Application received | | | 5/22/2006 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 5/22/2006 | | DONE |
|
|
|
|