Final | 7/10/2007 | 7/11/2007 | 7/11/2007 | P | FAIL |
Pat Lass
|
|
|
melissa Phone #: ###-#### AFCI breaker trips and doesn't control the bedroom.
|
Final | 12/27/2006 | 12/28/2006 | 12/28/2006 | P | FAIL |
Bob Reichert
|
|
|
jeff; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corrections not done, needs to install afci and strap gounding electrode conductor to house, rest ok
|
Final | 8/2/2006 | 8/3/2006 | 8/3/2006 | A | FAIL |
Bob Reichert
|
|
|
jeff- call prior to insp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley told owner, left corr notice, nec 408.4 complete and definitive circuit directory shall be provided in panels and identify smoke detector circuit, 210.12(B) arc-fault circuit interruptor shall be installed for bedroom, 110.3 panelboard deadfront screw shall be installed,230.28 service mast shall have guy kit installed
|
Electrical Rough-In | 6/21/2006 | 6/22/2006 | 6/22/2006 | A | PASS |
Jim Schmer
|
|
|
melissa ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
|
Electrical Rough-In | 6/21/2006 | 6/21/2006 | 6/21/2006 | P | FAIL |
Jack Frank
|
|
|
melissa; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr. all violations not corrected new ones created, 300.4 nail plates and 11/4", 300.14 6" free length, 110.14(B) shall use devices to splices cannot just twist them, new violation 314.17(C) and 334.30 secure cables within 8" of boxes, Jim S is at site too talk to owner about corrections job still needs r/i for other bath rm afci for bed rm circuits, guy for mast, grd pigtails for switches
|
Electrical Rough-In | 6/20/2006 | 6/20/2006 | 6/20/2006 | P | FAIL |
Jack Frank
|
|
|
Melissa; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corr. met owner 300.14 shall provide 6" free conductor short grd wires,, 300.4(A)(1)(D) nail plates and 11/4",250.148 splice all equip grds #14⽎.14(B) use device to splice all equip grds they are just twisted, 310.16 shall not use #14 switch legs and travelers on 20 amp circuit
|
Electrical Rough-In | 6/15/2006 | 6/15/2006 | 6/15/2006 | P | CANC |
Jack Frank
|
|
|
###-#### - melissa see added conference
|
Conference | 6/15/2006 | 6/15/2006 | 6/15/2006 | P | DONE |
Jack Frank
|
|
|
###-#### - melissa ok
|
Rough-In Permanent Service | 5/25/2006 | 5/26/2006 | 5/26/2006 | A | PASS |
Jack Frank
|
|
|
1st in am for electrode ok p/s o/h rec. ok
|
Electrical Rough-In | 5/25/2006 | 5/25/2006 | 5/25/2006 | P | PART |
Jack Frank
|
|
|
melissa bierman ###-#### conference only
|
Issue PAID IN FULL permit | | | 5/25/2006 | | DONE |
|
|
|
|
Application received | | | 5/25/2006 | | |
|
|
|
|