Final | 6/1/2006 | 6/1/2006 | 6/1/2006 | P | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Joseph Zumwalt wrong type insp, see t/s
|
Temporary Service | 6/1/2006 | 6/1/2006 | 6/1/2006 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Joseph Zumwalt corr made, t/s u/g n ok
|
Temporary Service | 5/31/2006 | 5/31/2006 | 5/31/2006 | P | FAIL |
Bob Reichert
|
|
|
###-#### - joe called contr, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 310.7 conductors used for direct burial shall be of a type identified for such use
|
Issue permit | | | 5/31/2006 | | |
|
|
|
|
Application received | | | 5/31/2006 | | |
|
|
|
|