First Notice | 6/8/2006 | 6/8/2006 | 6/12/2006 | | DONE |
William E Thomas
|
|
|
This permit finaled on the web by Tyler Bowen
|
Final | 6/8/2006 | 6/8/2006 | 6/8/2006 | P | PASS |
William E Thomas
|
|
|
final ok
|
Permanent Service | 6/8/2006 | 6/8/2006 | 6/8/2006 | P | PASS |
William E Thomas
|
|
|
Phone #: ###-#### Internet Inspection Request from: Tyler Bowen p/s u/g n ok
|
Permanent Service | 6/7/2006 | 6/7/2006 | 6/7/2006 | P | FAIL |
Jack Frank
|
|
|
TYLER; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy corr. called left message 200.6 shall not ID #6 or smaller neutral,, 110.3(B) shall use manufactures bond screw at p/s, listed equip grd bus at subpanel and terminate equip grds too it,manufactures breakers in subpanel, 110.12(A) seal KOs, 250.8 no SMS for grds or bonds 110.1(A) use sta-con stranded wire 5th terminal at meter
|
Final | 6/6/2006 | 6/7/2006 | 6/7/2006 | A | CANC |
Jack Frank
|
|
|
FINAL AND PERMANENT SERVICE TYLER; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy called contrctor requested wrong type of request
|
Electrical Rough-In | 6/1/2006 | 6/1/2006 | 6/1/2006 | P | PART |
Jack Frank
|
|
|
TYLER CALL PRIOR TO COMMING OUT CAN WE MAKE THIS YOUR LAST STOP TODAY; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy u/g ok this is behind 8109 w franklin east end
|
Application received | | | 6/1/2006 | | |
|
|
|
|
Issue & PRINT permit | | | 6/1/2006 | | DONE |
|
|
|
|