Final | 6/5/2006 | 6/6/2006 | 6/6/2006 | A | FAIL |
Jack Frank
|
|
|
A/C ready for final. Please contact Patrick Gill, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters corr. called a/c ok but subpanel where a/c is feed from and p/s are a mess work done by owner or contractor dought if there was permit or inspection, BCC no violation retained250.52,104 grd or bond p/s to water, 250.24(A)(5) isolate grds neutrals suubpanel, 312.5 conn for all cables, 110.12(A) seal unused openings, 240.51,52,53,54 shall install type S fuses and adapters where abuse over fusing circuits, 300.4(F) bushings for 4 and larger in raceways, 300.10 bond bushings where RE washers are used, 408.4 circut directory, 314.29 I think there is a buried LB or box behind p/s, or it might be open wiring
|
Application received | | | 6/5/2006 | | DONE |
|
|
|
This permit was created on the web by Wendy Waters
|