Final | 9/27/2007 | 9/27/2007 | 9/27/2007 | A | PASS |
Bob Reichert
|
|
|
this permit was in conjunction with home-owner ele06-01205, ok to final
|
Inspector's copy Ele permit | | | 10/9/2006 | | |
|
|
|
|
Permanent Service | 9/20/2006 | 9/20/2006 | 9/20/2006 | P | PASS |
Bob Reichert
|
|
|
This was called in incorrect before -should have been a RI/PERMANENT SERVICE NOT A PERMANET SERVICE SO IT IS NOW READY FOR A PERMANENT SERVICE PER JIM S. p/s o/h rec ok ok'd by 324 6-15-06, called ipco to confirm power apparently is on
|
Permanent Service | 6/15/2006 | 6/15/2006 | 6/15/2006 | P | PASS |
Jim Schmer
|
|
|
Work performed by Clayton Perry.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz
|
Permanent Service | 6/8/2006 | 6/9/2006 | 6/9/2006 | A | PASS |
William E Thomas
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer
|
Electrical Rough-In | 6/8/2006 | 6/9/2006 | 6/9/2006 | A | CANC |
William E Thomas
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer
|
Rough-In Permanent Service | 6/9/2006 | 6/9/2006 | 6/9/2006 | P | FAIL |
William E Thomas
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer 1. 110.26A1-- working clearences sub panel 2. 240.24D-- panel in closet 3. 300.4F-- bushings for sub panel 4. 314.17A-- broken box tabs nm 5. 314.17C-- 8" stapling for nm boxs 6. 300.4A1-- nail plates 7. 300.4D-- nm cable parallel to studs 8. B.C.C.-- All make up shall be complete prior to rough-in inspection.
|
Application received | | | 6/5/2006 | | DONE |
|
|
|
This permit was created on the web by Dana Moyer
|