Second Notice ELE | 3/2/2007 | 3/2/2007 | 3/19/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 2/1/2007 | 2/1/2007 | 3/2/2007 | | DONE |
Bob Reichert
|
|
|
|
Final | 1/31/2007 | 2/1/2007 | 2/1/2007 | P | PASS |
Bob Reichert
|
|
|
scott; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, ok to final
|
Final | 1/31/2007 | 1/31/2007 | 1/31/2007 | P | CANC |
Bob Reichert
|
|
|
scott; Phone #: ###-#### Internet Inspection Request from: Victoria Beall Inspection cancelled from web by: Victoria Beall
|
Final | 11/29/2006 | 11/29/2006 | 11/29/2006 | P | FAIL |
Bob Reichert
|
|
|
scott; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, nec 348.30 fmc shall be secured within 12" of box and not over 6' in length, 410.30(C)(1) cord connected fixtures shall be directly below outlet
|
Permanent Service | 10/18/2006 | 10/19/2006 | 10/19/2006 | A | PASS |
Pat Lass
|
|
|
scott ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith P/S U/G N OK
|
Permanent Service | 10/16/2006 | 10/16/2006 | 10/16/2006 | P | NR |
Mike Kinnear
|
|
|
scott; Phone #: ###-#### Internet Inspection Request from: Patricia Smith conf grounding 2 -- 200amp services
|
Electrical Rough-In | 10/4/2006 | 10/5/2006 | 10/5/2006 | A | PART |
Jack Frank
|
|
|
scott - underground trench insp; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok
|
Electrical Rough-In | 10/2/2006 | 10/3/2006 | 10/3/2006 | A | PART |
Jack Frank
|
|
|
scott Note: underground; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles u/g for light SE end of lot
|
Electrical Rough-In | 9/20/2006 | 9/20/2006 | 9/20/2006 | P | PART |
Jack Frank
|
|
|
scott - partial for walls ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley walls S E corner
|
Electrical Rough-In | 6/14/2006 | 6/14/2006 | 6/14/2006 | P | PART |
Jack Frank
|
|
|
jerod Note: uifer; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
Application received | | | 6/6/2006 | | |
|
|
|
|
Issue permit | | | 6/6/2006 | | DONE |
|
|
|
|