Final | 2/25/2008 | 2/25/2008 | 2/25/2008 | P | PASS |
Bob Reichert
|
|
|
ok to final
|
Permanent Service | 1/31/2007 | 1/31/2007 | 1/31/2007 | P | PASS |
Bob Reichert
|
|
|
gary ; Phone #: ###-#### Internet Inspection Request from: Darla Downs corr made, p/s o/h rec ok
|
Permanent Service | 1/30/2007 | 1/30/2007 | 1/30/2007 | A | FAIL |
Bob Reichert
|
|
|
Gary - ###-#### ok per Bob to put in for this am as he had an inspection there already///dld called, left corr notice, nec 408.4 circuit directory shall be complete, concise, clear, 348.30 fmc shall be strapped within 12" of box, 358.30 emt shall be strapped within 3' of box, 314.15 fittings in wet locations shall be listed for use in wet locations,314.28(C) covers shall be provided with suitable screws,BCC all make-up shall be done, range and dryer shall be 4-wire circuits
|
Final | 9/1/2006 | 9/5/2006 | 9/5/2006 | A | CANC |
Jack Frank
|
|
|
steve; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley contractor called nr, inspection was called in by owner
|
Issue & PRINT permit | | | 6/8/2006 | | DONE |
|
|
|
|
Application received | | | 6/7/2006 | | |
|
|
|
|