Telephone call | | | 3/14/2007 | | DONE |
|
|
|
lft ms with superior on the values on 2/7 8:10 no respond
|
Second Notice ELE | 8/4/2006 | 8/4/2006 | 8/10/2006 | | DONE |
|
|
|
This permit finaled on the web by Todd Holbrook
|
First Notice | 7/17/2006 | 7/17/2006 | 8/4/2006 | | DONE |
Bob Reichert
|
|
|
|
Final | 7/14/2006 | 7/17/2006 | 7/17/2006 | A | PASS |
Bob Reichert
|
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ok to final
|
Final | 7/14/2006 | 7/14/2006 | 7/14/2006 | P | FAIL |
Bob Reichert
|
|
|
chris ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called left corr notice,nec 300.11(A) boxes shall be securely fastened in place (ceiling cans), 210.62 showroom receptacle shall be provided, 110.22 each disconnect shall be legible and durable and marked and suitable for environment
|
Rough-In Permanent Service | 6/8/2006 | 6/8/2006 | 6/8/2006 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Todd Holbrook walls only ok to cover, p/s exst meter pak n ok
|
Application received | | | 6/8/2006 | | DONE |
|
|
|
This permit was created on the web by Todd Holbrook
|