Final | 2/21/2007 | 2/21/2007 | 2/21/2007 | P | PASS |
Bob Reichert
|
|
|
lauren; Phone #: ###-#### Internet Inspection Request from: Victoria Beall ok to final
|
Electrical Rough-In | 1/11/2007 | 1/11/2007 | 1/11/2007 | P | PASS |
Bob Reichert
|
|
|
lauren; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, ric ok
|
Electrical Rough-In | 1/10/2007 | 1/10/2007 | 1/10/2007 | P | FAIL |
Bob Reichert
|
|
|
lauren; Phone #: ###-#### Internet Inspection Request from: Victoria Beall called, left message, tried to explain 1 1/4" left and initialed card and corr notice
|
Electrical Rough-In | 1/9/2007 | 1/9/2007 | 1/9/2007 | P | FAIL |
William E Thomas
|
|
|
loren ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith 1. corrections still not made
|
Electrical Rough-In | 1/8/2007 | 1/8/2007 | 1/8/2007 | P | FAIL |
Bob Reichert
|
|
|
LOREN; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called, left message, left corr notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 210.52(A) receptacles shall be placed and spaced per 210.52(A)(1) thru (3), BCC permit shall be upgraded to 6 rooms
|
Application received | | | 6/8/2006 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 6/8/2006 | | DONE |
|
|
|
|