Second Notice ELE | 7/6/2006 | 7/6/2006 | 7/6/2006 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 6/15/2006 | 6/15/2006 | 7/6/2006 | | DONE |
Bob Reichert
|
|
|
|
Temporary Service | 6/14/2006 | 6/15/2006 | 6/15/2006 | A | PASS |
Bob Reichert
|
|
|
please contact Pat for temp power service, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters corr made, t/s u/g n ok
|
Temporary Service | 6/13/2006 | 6/14/2006 | 6/14/2006 | A | FAIL |
Bob Reichert
|
|
|
Please contact Pat, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters called, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection,250.24(A) gec shall be connected to gnded conductor terminal, 250.53(G) gnd electrode shall be driven at angle not to exceed 45 degree, BCC job id sticker shall be posted
|
Application received | | | 6/13/2006 | | DONE |
|
|
|
This permit was created on the web by Wendy Waters
|