Final | 8/29/2006 | 8/30/2006 | 8/30/2006 | A | PASS |
Bob Reichert
|
|
|
nick ###-#### ok to final
|
Electrical Rough-In | 6/16/2006 | 6/16/2006 | 6/16/2006 | P | PASS |
Bob Reichert
|
|
|
joe - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 6/15/2006 | 6/15/2006 | 6/15/2006 | P | FAIL |
Bob Reichert
|
|
|
###-#### - joe called, left corr notice, nec 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing member, 210.52(A)(1) recpts shall not be over 6' from each other measured along the floor line in any wall space,BCC all make-up shall be done,boxes installed for entry and bath,panel shall be put in a safe condition with cover
|
Issue permit | | | 6/15/2006 | | DONE |
|
|
|
|
Application received | | | 6/15/2006 | | |
|
|
|
|