Temporary Service | 6/16/2006 | 6/16/2006 | 6/16/2006 | P | PASS |
Bob Reichert
|
|
|
joe - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr made, t/s u/g n ok
|
Temporary Service | 6/15/2006 | 6/15/2006 | 6/15/2006 | P | FAIL |
Bob Reichert
|
|
|
###-#### - joe called, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 250.24 gec shall connect to grounded conductor terminal, 110.14(A) gec terminal shall be tight for thouroughly good connection, BCC job id sticker shall be posted,
|
Issue permit | | | 6/15/2006 | | DONE |
|
|
|
|
Application received | | | 6/15/2006 | | |
|
|
|
|