Final | 7/25/2006 | 7/26/2006 | 7/26/2006 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 7/25/2006 at 4:35:29 PM. Contact: ###-####. ok to final
|
Rough-In Permanent Service | 6/20/2006 | 6/21/2006 | 6/21/2006 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 6/20/2006 at 2:52:11 PM. Contact: ###-####. corr made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 6/16/2006 | 6/20/2006 | 6/20/2006 | A | FAIL |
Bob Reichert
|
|
|
steve ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called, left message, nec 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing member,314.20 in walls of combustible material, boxes shall be flush with finished surface or project therefrom.
|
Application received | | | 6/16/2006 | | |
|
|
|
|
Issue permit | | | 6/16/2006 | | DONE |
|
|
|
|