Final | 10/12/2006 | 10/12/2006 | 10/12/2006 | P | PASS |
Bob Reichert
|
|
|
ron; Phone #:- note: call for access- ###-#### Internet Inspection Request from: Patricia Smith called contr, ok to final
|
Electrical Rough-In | 6/22/2006 | 6/22/2006 | 6/22/2006 | P | PASS |
Bob Reichert
|
|
|
ron - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 6/21/2006 | 6/22/2006 | 6/22/2006 | A | FAIL |
Bob Reichert
|
|
|
ron; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called, left corr notice, nec 210.52(A)(1) recpts shall be installed so that no point is over 6' along wall space from a recpt outlet, 300.4(A)&(D) edge of holes and nm cable shall be 1 1/4" from edge of framing members,BCC all make-up shall be done
|
Application received | | | 6/21/2006 | | |
|
|
|
|
Issue permit | | | 6/21/2006 | | DONE |
|
|
|
|