Second Notice ELE | 12/26/2006 | 12/26/2006 | 1/8/2007 | | DONE |
|
|
|
This permit finaled on the web by Wendy Waters
|
First Notice | 12/12/2006 | 12/12/2006 | 12/26/2006 | | DONE |
Jack Frank
|
|
|
|
Final | 12/12/2006 | 12/12/2006 | 12/12/2006 | P | PASS |
Jack Frank
|
|
|
Ready for final on core & shell, please contact Dan, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters ok no card
|
Permanent Service | 12/4/2006 | 12/4/2006 | 12/4/2006 | P | PASS |
Jack Frank
|
|
|
service ready, please contact Dan, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters p/s u/g new ok
|
Electrical Rough-In | 12/1/2006 | 12/1/2006 | 12/1/2006 | P | FAIL |
Jack Frank
|
|
|
Please check meter cabinet. Please contact Dan thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters needs to address 200 amp tap off of 400 amp needs 200 amp O C device, also size of p/s increased to 1200 from 800, called
|
Permanent Service | 10/12/2006 | 10/13/2006 | 10/13/2006 | P | PASS |
Bob Reichert
|
|
|
Service inspection, please contact Dan, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters p/s u/g n ok for house panel only, contr needs to get ti permits
|
Electrical Rough-In | 10/5/2006 | 10/6/2006 | 10/6/2006 | A | PASS |
Bob Reichert
|
|
|
Reinspect underground, please contact Dan, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters dug up u/g for inspection, ok to cover, green sticker on window
|
Electrical Rough-In | 10/4/2006 | 10/5/2006 | 10/5/2006 | A | FAIL |
Bob Reichert
|
|
|
Underground inspection, please contact Dan, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters called, left message, BCC all u/g shall be inspected before cover, nec 300.5 rnc shall be minimum 24" under parking and drive areas
|
Electrical Rough-In | 10/2/2006 | 10/3/2006 | 10/3/2006 | A | PASS |
Bob Reichert
|
|
|
Interior wall cover, please contact Dan, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters elect room and bath walls only ok to cover
|
Electrical Rough-In | 9/18/2006 | 9/19/2006 | 9/19/2006 | A | PART |
Bob Reichert
|
|
|
dan ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley exterior walls only ok to cover
|
ELE-Aging Inspection | 8/23/2006 | 8/23/2006 | 8/23/2006 | | DONE |
Bob Reichert
|
|
|
suc
|
Electrical Rough-In | 6/21/2006 | 6/23/2006 | 6/23/2006 | P | PASS |
Bob Reichert
|
|
|
underground inspection, please contact Miles, thank you; Phone #: ###-#### Internet Inspection Request from: Wendy Waters gec only ok to cover
|
Electrical Rough-In | 6/21/2006 | 6/22/2006 | 6/21/2006 | P | CANC |
Bob Reichert
|
|
|
Underground inspection; Phone #: ###-#### Inspection cancelled from web by: Wendy Waters
|
Owner Supplied Equipment | | | 6/21/2006 | | |
|
|
|
|
Application received | | | 6/21/2006 | | DONE |
|
|
|
This permit was created on the web by Wendy Waters
|