Third Notice ELE | 3/2/2007 | 3/2/2007 | 3/7/2007 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Second Notice ELE | 2/9/2007 | 2/9/2007 | 3/2/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 1/11/2007 | 1/11/2007 | 2/9/2007 | | DONE |
Bob Reichert
|
|
|
|
Final | 1/10/2007 | 1/11/2007 | 1/11/2007 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 1/10/2007 at 3:09:52 PM. Contact: ###-####. approval on listing ok, ok to final, signed occ card
|
Final | 1/8/2007 | 1/9/2007 | 1/9/2007 | A | NR |
Bob Reichert
|
|
|
wayne - please call 1/2 hr prior to inspection ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith labels still not correct for luminaires
|
Final | 1/2/2007 | 1/2/2007 | 1/2/2007 | P | PART |
Jack Frank
|
|
|
listing for pool heaters ok, still needs to resolve listing of tanning beds
|
Final | 12/27/2006 | 12/27/2006 | 12/27/2006 | P | PART |
Jack Frank
|
|
|
wayne ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith T/O ok only corr. posted for pool heaters 3 of them, and all Ambition 250 super power tanning beds shall be locked out and shall not be used till listing problems are corrected, BCC 4.05.(33A) nec 110.2 listed ,labeled, and approved
|
Final | 12/26/2006 | 12/27/2006 | 12/27/2006 | A | NR |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 12/26/2006 at 6:23:07 PM. Contact: ###-####. need listing information for pool heaters, 3 of them and small tanning beds etl listing is for sun/heat lamps only
|
Final | 12/26/2006 | 12/26/2006 | 12/26/2006 | P | CANC |
Pat Lass
|
|
|
Wayne; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett not ready
|
Final | 12/22/2006 | 12/26/2006 | 12/26/2006 | A | NR |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 12/22/2006 at 4:44:15 PM. Contact: ###-####.
|
Final | 12/22/2006 | 12/22/2006 | 12/22/2006 | P | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 12/22/2006 at 7:59:13 AM. Contact: ###-####. no card signed, made list with contr of misc corrections, look for labels on some tanning booths, finish gfci in bath, add sw plates, strap mc, emt, water pipe over elect equip, provide common trip bkr for furniture, will call back next week, contr has list to walk thru
|
Electrical Rough-In | 12/14/2006 | 12/14/2006 | 12/14/2006 | P | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 12/14/2006 at 7:49:57 AM. Contact: ###-####. ok cover ceiling only
|
Conference | 12/12/2006 | 12/12/2006 | 12/12/2006 | P | DONE |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 12/12/2006 at 7:21:44 AM. Contact: ###-####. talked about buck-boost xfmrs, application ok, physical install up to contractor
|
Conference | 12/8/2006 | 12/11/2006 | 12/11/2006 | A | DONE |
Bob Reichert
|
|
|
WAYNE nOTE: EARLY EARLY; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles met contr, talked about application of buck- boost transformers, and pool lights. Lights ok, don't need gfci.
|
Electrical Rough-In | 11/17/2006 | 11/17/2006 | 11/17/2006 | P | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 11/17/2006 at 10:03:24 AM. Contact: ###-####. recpt area walls ok to cover
|
Permanent Service | 11/14/2006 | 11/15/2006 | 11/16/2006 | A | PASS |
Bob Reichert
|
|
|
or ###-#### blake or wayne; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover sauna walls except for controller, told elect to ground and bond separately derived system,nec 250.30, p/s u/g n ok
|
Permanent Service | 11/13/2006 | 11/13/2006 | 11/13/2006 | P | CANC |
Bob Reichert
|
|
|
###-#### - wayne; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
Electrical Rough-In | 11/9/2006 | 11/9/2006 | 11/9/2006 | P | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 11/9/2006 at 11:17:56 AM. Contact: ###-####. front soffits and inside sign ckt ok to cover
|
Electrical Rough-In | 10/27/2006 | 10/27/2006 | 10/27/2006 | P | PART |
Pat Lass
|
|
|
wayne; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie partial Wall R/I Gym and office restroom area in frontboth floors.
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 10/27/2006 | | |
|
|
|
needed ele insp
|
Electrical Rough-In | 10/18/2006 | 10/19/2006 | 10/19/2006 | A | PASS |
Jim Schmer
|
|
|
Scheduled by a contractor via Hello! on 10/18/2006 at 3:42:20 PM. Contact: ###-####. pool walls only
|
Electrical Rough-In | 10/6/2006 | 10/9/2006 | 10/9/2006 | A | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 10/6/2006 at 4:08:14 PM. Contact: ###-####. ok cover walls only tanning & equip. rms sw corner of building
|
Electrical Rough-In | 10/4/2006 | 10/5/2006 | 10/5/2006 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/4/2006 at 2:50:05 PM. Contact: ###-####. front outside u/g and lights
|
Electrical Rough-In | 9/28/2006 | 9/29/2006 | 9/29/2006 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 9/28/2006 at 5:14:26 PM. Contact: ###-####. west end exercise and spinning rms, common wall, east end exercise and corridor walls ok
|
Electrical Rough-In | 9/25/2006 | 9/25/2006 | 9/25/2006 | P | PART |
Jack Frank
|
|
|
blake or ###-#### wayne ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie N E restrms walls hard ceilings, SE front wall
|
Electrical Rough-In | 9/15/2006 | 9/15/2006 | 9/15/2006 | P | PART |
Pat Lass
|
|
|
###-####. Scheduled by a contractor via Hello! on 9/15/2006 at 8:28:21 AM. Contact: ###-####. mens restroom ok
|
Electrical Rough-In | 8/18/2006 | 8/18/2006 | 8/18/2006 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 8/18/2006 at 9:42:07 AM. Contact: ###-####. E grid pool and spa ok
|
Electrical Rough-In | 7/31/2006 | 8/1/2006 | 8/1/2006 | A | PART |
Jack Frank
|
|
|
BLAKE; Phone #: ###-#### Internet Inspection Request from: Darla Downs u/g conduit in front and pool spa lights
|
Electrical Rough-In | 7/26/2006 | 7/26/2006 | 7/26/2006 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 7/26/2006 at 8:29:39 AM. Contact: ###-####. u/g panel rm ok
|
Electrical Rough-In | 7/20/2006 | 7/20/2006 | 7/20/2006 | P | PART |
Pat Lass
|
|
|
###-####. Scheduled by a contractor via Hello! on 7/20/2006 at 11:16:14 AM. Contact: ###-####. south west parking lot u/G ok
|
Electrical Rough-In | 7/14/2006 | 7/14/2006 | 7/14/2006 | P | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 7/14/2006 at 11:22:42 AM. Contact: ###-####. ok to cover se part running ns and ew from temp office and center of lot about 30' by center light
|
Electrical Rough-In | 7/13/2006 | 7/13/2006 | 7/13/2006 | P | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 7/13/2006 at 11:09:47 AM. Contact: ###-####. Underground on south side 2/3rds up from the building's east end
|
Electrical Rough-In | 7/12/2006 | 7/12/2006 | 7/12/2006 | P | PART |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 7/12/2006 at 9:01:20 AM. Contact: ###-####. ok cover under ground conduit northeast side of parking lot
|
Electrical Rough-In | 7/5/2006 | 7/6/2006 | 7/6/2006 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 7/5/2006 at 3:46:44 PM. Contact: ###-####. pool & spa bond only no equip. grid
|
Electrical Rough-In | 6/30/2006 | 6/30/2006 | 6/30/2006 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/30/2006 at 11:19:17 AM. Contact: ###-####. u/g service and phone conduits
|
Electrical Rough-In | 6/29/2006 | 6/29/2006 | 6/29/2006 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/29/2006 at 10:59:19 AM. Contact: ###-####. S W building u/g ok
|
Application received | | | 6/23/2006 | | |
|
|
|
|
Issue permit | | | 6/23/2006 | | DONE |
|
|
|
|