Final | 8/25/2006 | 8/25/2006 | 8/25/2006 | A | PASS |
Jack Frank
|
|
|
ok
|
Rough-In Permanent Service | 8/24/2006 | 8/25/2006 | 8/25/2006 | A | PASS |
Jack Frank
|
|
|
gary; Phone #: ###-#### Internet Inspection Request from: Darla Downs p/s o/h rec. ok
|
Permanent Service | 7/6/2006 | 7/7/2006 | 7/7/2006 | A | FAIL |
Jack Frank
|
|
|
Gary; Phone #: ###-#### Internet Inspection Request from: Darla Downs corr. called 110.3(B) use sq d breakers only, 250.66&250.104 all water bonding shall be #4, 250.24 remove old water bond from sub panel, 312.5 conn. for grd wires, 408.4 panel directory
|
Permanent Service | 6/27/2006 | 6/28/2006 | 6/28/2006 | A | CANC |
Jack Frank
|
|
|
gary; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles contractor called
|
Application received | | | 6/27/2006 | | |
|
|
|
|
Issue permit | | | 6/27/2006 | | |
|
|
|
|
Rough-In Permanent Service | 8/25/2006 | 8/25/2006 | | A | |
|
|
|
ok per Jack Frank to put in for this morning.
|