Final | 10/20/2006 | 10/20/2006 | 10/20/2006 | P | PASS |
Bob Reichert
|
|
|
access code 6675; Phone #: ###-#### Internet Inspection Request from: Joe Thomas corr made, ok to final
|
Final | 10/12/2006 | 10/13/2006 | 10/13/2006 | A | FAIL |
Jack Frank
|
|
|
GARAGE CODE IS 6675; Phone #: ###-#### Internet Inspection Request from: Joe Thomas corr fee due called, 314.16 box fill island also protect romex in island cabinet, 314.43 no screws in plastic boxes MBath, 210.8 gfci for all garage recepts, reversed polarity hall bath , note needs to check all recepts, remove access panel at j tub
|
Reinspection Fee (no hold) | 10/13/2006 | 10/13/2006 | 10/13/2006 | P | DONE |
Jack Frank
|
|
|
GARAGE CODE IS 6675; Phone #: ###-#### Internet Inspection Request from: Joe Thomas corr fee due
|
Rough-In Permanent Service | 6/27/2006 | 6/28/2006 | 6/28/2006 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas called outlet in pantry shall be S. A. B. C. address clearence S W basement bed rm closet light r/i p/s u/g new ok
|
Application received | | | 6/27/2006 | | DONE |
|
|
|
This permit was created on the web by Joe Thomas
|