Final | 10/16/2007 | 10/16/2007 | 10/16/2007 | P | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson ok final
|
Permanent Service | 11/30/2006 | 12/1/2006 | 12/1/2006 | P | PASS |
Jack Frank
|
|
|
service change; Phone #: ###-#### Internet Inspection Request from: Therrin Robertson u/g new ok
|
Electrical Rough-In | 7/12/2006 | 7/12/2006 | 7/12/2006 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson corrections made, ric ok
|
Electrical Rough-In | 7/10/2006 | 7/11/2006 | 7/11/2006 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called left message left corr notice, nec 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members or shall be protected with steel plates, 334.30 nm cable shall be supported and secured within 12" of panel, 210.52(C)(1) recpts shall be within 2' of sink BCC alll make-up shall be done,approved set of plans shall be on job,Note: is new panel service or subpanel?
|
Application received | | | 7/10/2006 | | DONE |
|
|
|
This permit was created on the web by Therrin Robertson
|