Final | 9/26/2006 | 9/27/2006 | 9/27/2006 | A | PASS |
Bob Reichert
|
|
|
stephen; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
|
Electrical Rough-In | 7/12/2006 | 7/13/2006 | 7/13/2006 | A | PASS |
Bob Reichert
|
|
|
verna - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ric ok, p/s u/g n ok
|
Electrical Rough-In | 7/12/2006 | 7/12/2006 | 7/12/2006 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 7/12/2006 at 7:58:10 AM. Contact: ###-####. called, left message, nec 312.5 all conductors entering enclosures shall have abrasion protection, 334.80 where more than 2 nm cables are bundled and pass thru wood framing that is to be fire-or draft stopped, the ampacity shall be adjusted per 310.15(B)(2)(a), 314.20 in walls constructed of wood or other combustible material boxes shall be flush with the finished surface
|
Application received | | | 7/10/2006 | | |
|
|
|
|
Issue permit | | | 7/10/2006 | | DONE |
|
|
|
|