Final | 9/19/2006 | 9/19/2006 | 9/19/2006 | P | PASS |
Bob Reichert
|
|
|
spencer; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ok to final
|
Final | 9/12/2006 | 9/12/2006 | 9/12/2006 | P | FAIL |
Bob Reichert
|
|
|
spencer; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie--call 1st for access called, left corr notice, nec 250.53(G) electrode shall be flush with or below ground ,406.5&404.9 faceplates shall seat against mounting surface, 406.4 recpts shall be securely fastened in place, 404.4 switch shall not be installed in tub space, BCC tile work shall be done in bath
|
Rough-In Permanent Service | 7/11/2006 | 7/11/2006 | 7/11/2006 | P | PASS |
Bob Reichert
|
|
|
shelly; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ric ok, p/s u/g n ok
|
Application received | | | 7/11/2006 | | |
|
|
|
|
Issue permit | | | 7/11/2006 | | DONE |
|
|
|
|