Temporary Service | 7/18/2006 | 7/18/2006 | 7/18/2006 | P | PASS |
Bob Reichert
|
|
|
zane ###-#### t/s o/h n ok
|
Temporary Service | 7/18/2006 | 7/18/2006 | 7/18/2006 | P | CANC |
Bob Reichert
|
|
|
###-####- zane -re-insp--need to pay re-insp fee 1st
|
Stop Work/Reinspection Fee | 7/14/2006 | 7/14/2006 | 7/18/2006 | P | DONE |
Bob Reichert
|
|
|
see fail,t/s
|
Temporary Service | 7/14/2006 | 7/14/2006 | 7/14/2006 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 7/14/2006 at 11:26:28 AM. Contact: ###-####. called, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 230.24(B)(1) lowest point of drip loop for service shall be 10' above finished grade
|
Application received | | | 7/12/2006 | | DONE |
|
|
|
This permit was created on the web by Zane Robertson
|