Third Notice ELE | 3/2/2007 | 3/2/2007 | 3/28/2007 | | DONE |
|
|
|
This permit finaled on the web by Celinda Winters
|
Second Notice ELE | 2/9/2007 | 2/9/2007 | 3/2/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 1/3/2007 | 1/3/2007 | 2/9/2007 | | DONE |
Jack Frank
|
|
|
|
Final | 1/3/2007 | 1/3/2007 | 1/3/2007 | P | PASS |
Jack Frank
|
|
|
jeff - late as possible ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok card signed
|
Final | 12/29/2006 | 1/2/2007 | 1/2/2007 | A | FAIL |
Jack Frank
|
|
|
Address is now on the building - the key for access can be picked up at Ted Mason Office at 1883 N. Wildwood or call Jeff at the above phone number and he will meet you there and open the building.; Phone #: ###-#### Internet Inspection Request from: Celinda Winters corr. called 400.8 cords shall not pass through ceiling, 410.30 (C) cords for fixtures shall be use listed canopy or use recept and cord cap, 314.27(D) use fan box or support fan to structure, how are hung?
|
Reinspection Fee (no hold) | 1/2/2007 | 1/2/2007 | 1/2/2007 | P | DONE |
Jack Frank
|
|
|
Address is now on the building - the key for access can be picked up at Ted Mason Office at 1883 N. Wildwood or call Jeff at the above phone number and he will meet you there and open the building.; Phone #: ###-#### Internet Inspection Request from: Celinda Winters fee due corr.
|
Final | 12/22/2006 | 12/26/2006 | 12/26/2006 | A | NH |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters called, told contr to put in notes how to have access
|
ELE-Aging Inspection | 11/8/2006 | 11/8/2006 | 11/8/2006 | | PART |
Jack Frank
|
|
|
wsuc
|
Permanent Service | 9/8/2006 | 9/8/2006 | 9/8/2006 | A | PASS |
Bob Reichert
|
|
|
p/s u/g n ok
|
Electrical Rough-In | 8/23/2006 | 8/24/2006 | 8/24/2006 | A | PASS |
Bob Reichert
|
|
|
Partial rough-in steel stud walls only Contact Ric; Phone #: ###-#### Internet Inspection Request from: Celinda Winters ok to cover walls only plus bath lid
|
Electrical Rough-In | 8/16/2006 | 8/17/2006 | 8/17/2006 | A | FAIL |
Bob Reichert
|
|
|
Wall Rough-in; Phone #: ###-#### Internet Inspection Request from: Celinda Winters called contr, left corr notice, nec 334.30 fmc shall be secured within 12" of box, 333.30 mc shall be strapped within 12" of box, 358.30(A) emt shall be secured within 3' of box, BCC address shall be posted, approved set of plans shall be on job, job id sticker shall be posted
|
Electrical Rough-In | 7/31/2006 | 7/31/2006 | 7/31/2006 | P | PASS |
Mike Kinnear
|
|
|
Rough-in for under slab - document from owner and architect in contractors possession.; Phone #: ###-#### Internet Inspection Request from: Celinda Winters ok cover under slab conduit.
|
Conference | 7/25/2006 | 7/26/2006 | 7/26/2006 | P | DONE |
Bob Reichert
|
|
|
General contractor would like to conference about the classification. Please call with a meeting time.; Phone #: ###-#### Internet Inspection Request from: Celinda Winters met contr and elect to discuss a letter stating purpose of garage
|
Electrical Rough-In | 7/17/2006 | 7/19/2006 | 7/19/2006 | A | NR |
Bob Reichert
|
|
|
underground rough-in ; Phone #: ###-#### Internet Inspection Request from: Celinda Winters left correction notice to builder, nec art 511 shall apply, therefore an area classification drawing shall be provided
|
Owner Supplied Equipment | | | 7/17/2006 | | |
|
|
|
|
Application received | | | 7/17/2006 | | DONE |
|
|
|
This permit was created on the web by Celinda Winters
|