Final | 11/1/2006 | 11/2/2006 | 11/2/2006 | A | PASS |
Jack Frank
|
|
|
spencer -re-insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok
|
Final | 10/19/2006 | 10/19/2006 | 10/19/2006 | P | FAIL |
Bob Reichert
|
|
|
spencer; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left corr notice, nec 210.52(A) 2' wall in kitchen shall have recpt installed, 210.8(A)(7) recpt for washer shall be gfci, 410.4(D) fixture within 3' of shower area shall be listed for damp location, 408.4 circuit directory shall be clear, concise and detailed to load served, 440.12(A) a/c breakers shall be per nameplate on unit
|
Final | 10/2/2006 | 10/3/2006 | 10/3/2006 | A | CANC |
Bob Reichert
|
|
|
steven; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called, left message, could not tell which house, no address posted
|
Electrical Rough-In | 7/31/2006 | 8/1/2006 | 8/1/2006 | A | PASS |
Bob Reichert
|
|
|
shelly; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ric ok
|
Rough-In Permanent Service | 7/28/2006 | 7/28/2006 | 7/28/2006 | P | CANC |
Bob Reichert
|
|
|
shelly - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley see p/s and ri
|
Electrical Rough-In | 7/28/2006 | 7/28/2006 | 7/28/2006 | P | FAIL |
Bob Reichert
|
|
|
called contr, left corr notice, nec 210.52(A)(2) recpt shall be installed in 2' wall space (rear entry), 300.4(A) edge of holes shall be 1 1/4" from edge of framing member, 414.20 in walls of combustible material, boxes shall be flush with finished surface BCC all make-up shall be done-kitchen
|
Permanent Service | 7/28/2006 | 7/28/2006 | 7/28/2006 | P | PASS |
Bob Reichert
|
|
|
shelly - reinsp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley p/s u/g n ok
|
Electrical Rough-In | 7/27/2006 | 7/28/2006 | 7/28/2006 | A | CANC |
Bob Reichert
|
|
|
shelly; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, no address
|
Application received | | | 7/27/2006 | | |
|
|
|
|
Issue permit | | | 7/27/2006 | | DONE |
|
|
|
|