Final | 9/22/2006 | 9/22/2006 | 9/22/2006 | P | PASS |
Bob Reichert
|
|
|
tim; Phone #: ###-#### Internet Inspection Request from: Barbara Stitt ok to final, left survey, nec 210.52(C)(1) kitchen counter outlets shall be spaced such that no point is more than 2' from an outlet, 406.4(D) recpts faces shall be flush with faceplate, called contr
|
Rough-In Permanent Service | 8/1/2006 | 8/1/2006 | 8/1/2006 | P | PASS |
Bob Reichert
|
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ric ok, p/s u/g n ok
|
Application received | | | 8/1/2006 | | |
|
|
|
|
Issue permit | | | 8/1/2006 | | DONE |
|
|
|
|