Second Notice ELE | 9/13/2006 | 9/13/2006 | 9/13/2006 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 8/29/2006 | 8/29/2006 | 9/13/2006 | | DONE |
Jack Frank
|
|
|
|
Temporary Service | 8/29/2006 | 8/29/2006 | 8/29/2006 | P | PASS |
Jack Frank
|
|
|
kevin; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley t/s u/g new ok
|
Reinspection Fee (no hold) | 8/24/2006 | 8/24/2006 | 8/25/2006 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jari Rivers fee due corr. posted called pass ok per JSchmer
|
Temporary Service | 8/23/2006 | 8/24/2006 | 8/24/2006 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jari Rivers corr. fee due called 312.5, 250.64(E) use plastic conn or listed grd conn for GEC, 250.53(G) shall install grd rod as code noted states, 110.12(C) clean dirt from t/s removed conn left in t/s on hot lugs
|
Application received | | | 8/4/2006 | | |
|
|
|
|
Issue permit | | | 8/4/2006 | | DONE |
|
|
|
|