Third Notice ELE | 5/14/2007 | 5/14/2007 | 6/20/2007 | | DONE |
|
|
|
This permit finaled on the web by Jari Rivers
|
Second Notice ELE | 4/24/2007 | 4/24/2007 | 5/14/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 4/11/2007 | 4/11/2007 | 4/24/2007 | | DONE |
William E Thomas
|
|
|
|
Final | 4/10/2007 | 4/11/2007 | 4/11/2007 | A | PASS |
William E Thomas
|
|
|
Phone #: ###-#### final ok
|
Final | 4/3/2007 | 4/5/2007 | 4/5/2007 | A | PART |
Bob Reichert
|
|
|
jerri; Phone #: ###-#### Internet Inspection Request from: Patricia Smith walked with elect left list such as labels, warning signs,ground gen set, FACP does not have proper clearance, pole lights need ground lugs, lights, recpts ok, they are working on owner's punch list
|
Electrical Rough-In | 3/22/2007 | 3/23/2007 | 3/23/2007 | A | PASS |
Bob Reichert
|
|
|
reinspection ceiling Phone #: ###-#### corrections made, ok to cover grid ceilings
|
Electrical Rough-In | 3/21/2007 | 3/22/2007 | 3/22/2007 | A | FAIL |
Bob Reichert
|
|
|
Cover on ceiling Phone #: ###-#### called, left correction notice,nec 330.30(B) mc cable shall be strapped within 12" of box, 358.30(A) emt shall be strapped within 3' of box, 110.12(A) unused openings in boxes shall be closed, 410.14(A) fixtures shall not be cord connected unless permitted by 410.30(B) or(C), 348.30 fmc shall be securely fastened by approved means, BCC no ceiling cover shall be done prior to inspection, no lv cables shall be on grid or raceways
|
Electrical Rough-In | 2/6/2007 | 2/8/2007 | 2/8/2007 | A | PASS |
Bob Reichert
|
|
|
electrial cover upstairs Phone #: ###-#### high bay area ok to cover clgs, (apparatus area)
|
Electrical Rough-In | 1/24/2007 | 1/25/2007 | 1/25/2007 | A | PART |
Jack Frank
|
|
|
james; Phone #: ###-#### Internet Inspection Request from: Victoria Beall 1st floor walls hard ceilings map rm, fire pole corridor, exercise rm and restrms
|
Permanent Service | 12/29/2006 | 12/29/2006 | 12/29/2006 | P | PASS |
Bob Reichert
|
|
|
service inspection; Phone #: ###-#### Internet Inspection Request from: Jari Rivers p/s u/g n ok
|
Electrical Rough-In | 12/19/2006 | 12/22/2006 | 12/22/2006 | P | PASS |
Mike Kinnear
|
|
|
Upstairs cover inspection & service inspection; Phone #: ###-#### Internet Inspection Request from: Jari Rivers ok cover ri 2nd floor only
|
Electrical Rough-In | 10/3/2006 | 10/3/2006 | 10/3/2006 | P | PART |
Jack Frank
|
|
|
Ufer ground inspection ; Phone #: ###-#### Internet Inspection Request from: Jari Rivers electrode ok
|
Electrical Rough-In | 8/29/2006 | 8/30/2006 | 8/30/2006 | P | PASS |
William E Thomas
|
|
|
Inground inspection; Phone #: ###-#### Internet Inspection Request from: Jari Rivers underground ok to generator
|
Electrical Rough-In | 8/29/2006 | 8/29/2006 | 8/29/2006 | P | PART |
Jack Frank
|
|
|
ground PVC cover inspection; Phone #: ###-#### Internet Inspection Request from: Jari Rivers part. u/g ok for u/g from xformer to building
|
Electrical Rough-In | 8/28/2006 | 8/29/2006 | 8/29/2006 | A | PART |
Jack Frank
|
|
|
cover for pvc ground & UFER Ground inspection; Phone #: ###-#### Internet Inspection Request from: Jari Rivers electrode only u/g not ready
|
Application received | | | 8/4/2006 | | |
|
|
|
|
Issue permit | | | 8/4/2006 | | DONE |
|
|
|
|