Second Notice ELE | 3/2/2007 | 3/2/2007 | 3/7/2007 | | DONE |
|
|
|
This permit finaled on the web by Joseph Zumwalt
|
First Notice | 2/7/2007 | 2/7/2007 | 3/2/2007 | | DONE |
Jack Frank
|
|
|
|
Final | 2/6/2007 | 2/7/2007 | 2/7/2007 | P | PASS |
Jack Frank
|
|
|
joe; Phone #: ###-#### call for key location Internet Inspection Request from: Victoria Beall corrections made ok no card
|
Final | 1/30/2007 | 1/31/2007 | 1/31/2007 | A | FAIL |
Jack Frank
|
|
|
Call Joe for key ###-#### or Pat at ###-#### Phone #: ###-#### boxes loose micro wave outlets, 110.12(C) some panels internal part, buses have paint on them bad gfci called outside fixtures loose
|
ELE-Aging Inspection | 11/15/2006 | 11/15/2006 | 11/15/2006 | | CANC |
Jack Frank
|
|
|
|
Rough-In Permanent Service | 9/14/2006 | 9/14/2006 | 9/14/2006 | P | PASS |
Bob Reichert
|
|
|
ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 8/22/2006 | 8/22/2006 | 8/22/2006 | P | FAIL |
Bob Reichert
|
|
|
Joe; Phone #: ###-#### Internet Inspection Request from: Joseph Zumwalt called contr, left corr notice, nec 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 314.20 in walls of combustible material, boxes shall be flush with finished surface, 110.26(A) there shall be no foreign wiring in work space about panels, BCC address shall be posted, approved plans shall be on job, units and respective meters shall be identified, all make-up shall be done-fixtures installed
|
Application received | | | 8/7/2006 | | DONE |
|
|
|
This permit was created on the web by Joseph Zumwalt
|