Second Notice ELE | 3/2/2007 | 3/2/2007 | 3/7/2007 | | DONE |
|
|
|
This permit finaled on the web by Don Lustig
|
First Notice | 2/8/2007 | 2/8/2007 | 3/2/2007 | | DONE |
Bob Reichert
|
|
|
|
Final | 2/8/2007 | 2/8/2007 | 2/8/2007 | P | PASS |
Bob Reichert
|
|
|
Meter in place light poles have power Phone #: ###-#### called, left survey, nec 410.15(B)(1) pole handholes shall be raintight
|
Rough-In Permanent Service | 12/11/2006 | 12/11/2006 | 12/11/2006 | P | PASS |
Bob Reichert
|
|
|
don - note: underground rough-in also ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith u/g ok to cover from service to junction box, p/s u/g n ok
|
Permanent Service | 12/11/2006 | 12/11/2006 | 12/11/2006 | P | CANC |
Bob Reichert
|
|
|
don - note: underground rough-in also ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith wrong type request, see rip
|
Electrical Rough-In | 8/11/2006 | 8/11/2006 | 8/11/2006 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 8/11/2006 at 10:56:04 AM. Contact: ###-####. u/g ok
|
Electrical Rough-In | 8/10/2006 | 8/10/2006 | 8/10/2006 | A | PART |
Jack Frank
|
|
|
I did an internet request yesterday for am but it did not post if already inspected ignore. Underground only concreate parking lot sides get 12inches more dirt to grade Thanks; Phone #: ###-#### Internet Inspection Request from: Don Lustig u/g in planter areas ok u/g in parking area needs 24" no cover
|
Application received | | | 8/9/2006 | | DONE |
|
|
|
This permit was created on the web by Don Lustig
|