Final | 8/11/2006 | 8/11/2006 | 8/11/2006 | P | PASS |
Bob Reichert
|
|
|
after 12:00pm please; Phone #: ###-#### Internet Inspection Request from: Shane Vigil corrections made, survey nec 680.26(B)(5) bond metal pipe for moved light fixture, ok to final
|
Final | 8/10/2006 | 8/11/2006 | 8/11/2006 | A | FAIL |
Bob Reichert
|
|
|
please call if you have questions. hot tub; Phone #: ###-#### Internet Inspection Request from: Shane Vigil called contr, left corr notice, nec 680.22(A)(3) recpt shall not be over 20' from inside wall of pool and not less than 10', 680.22(B)(3) existing fixture less than 5' from inside wall of pool shall be gfci protected
|
Application received | | | 8/10/2006 | | DONE |
|
|
|
This permit was created on the web by Shane Vigil
|