Final | 1/10/2007 | 1/11/2007 | 1/11/2007 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### called about covers, ok to final
|
Electrical Rough-In | 8/22/2006 | 8/22/2006 | 8/22/2006 | P | PASS |
Jack Frank
|
|
|
Late afternoon best if possible; Phone #: ###-#### Internet Inspection Request from: Curtis Dunham ok
|
Electrical Rough-In | 8/21/2006 | 8/21/2006 | 8/21/2006 | P | FAIL |
Jack Frank
|
|
|
I am going to be replacing the panel in the garage and would like to know if the panel feed can be reconnected as it is or if it needs to be changed. thanks Curtis; Phone #: ###-#### Internet Inspection Request from: Curtis Dunham corr. met contr, 300.4 nail plates and 11/4", 314,43 no screws allowed in plastic boxes, 210.52(A) needs required outlet spacing all areas, 300.14 6" of wire for all splices, address sub panel, dryer, range 4/wire, B C C complete all make up
|
Application received | | | 8/11/2006 | | DONE |
|
|
|
This permit was created on the web by Curtis Dunham
|