Conference | 2/5/2007 | 2/5/2007 | 2/5/2007 | P | DONE |
Bob Reichert
|
|
|
SERGEY ; Phone #: ###-#### Internet Inspection Request from: Darla Downs ok to extend permit per 324
|
Electrical Rough-In | 10/24/2006 | 10/24/2006 | 10/24/2006 | P | PASS |
Bob Reichert
|
|
|
sergey; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ric ok ,need to see service ltr
|
Electrical Rough-In | 9/15/2006 | 9/18/2006 | 9/18/2006 | A | FAIL |
Jack Frank
|
|
|
sergey; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles all violations not corrected and new one created, also not ready, 300.4 nail plates, 314.16 box fill, still needs calculations for circuits for new addition and service, 110.14(B) shall use approved tool for crimps loose equip grds told owner if corrections not made we will have to secure contractor
|
Electrical Rough-In | 8/30/2006 | 9/5/2006 | 9/5/2006 | A | FAIL |
Jack Frank
|
|
|
Sergey; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corr. met owner 210.52(A) needs outlet 2ft wall MBed rm, 410.8 clearence MB closet, 210.11(C)(3) shall provide required circuit, or circuits for bath rms, 300.4 (A)(1)&(D) prvide nail plates and 11/4" 210.70 (A)(2) (b) switch at exit door for outside light, 220.12&16 shall calc out reqired circuits for new addition, 408.41 only 1 neutral per terminal , B C C complete all makeup and grd pigtails for recepts and switches
|
Application received | | | 8/11/2006 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 8/11/2006 | | DONE |
|
|
|
|
ELE-Request for Extension | 2/5/2007 | 2/6/2006 | | A | |
Bob Reichert
|
|
|
pls extend
|