Second Notice ELE | 12/26/2006 | 12/26/2006 | 12/29/2006 | | DONE |
|
|
|
This permit finaled on the web by Sean DeLacy
|
First Notice | 10/9/2006 | 10/9/2006 | 12/26/2006 | | DONE |
Jack Frank
|
|
|
|
Final | 10/9/2006 | 10/9/2006 | 10/9/2006 | P | PASS |
Jack Frank
|
|
|
Paul Klindt; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok no card
|
Final | 10/6/2006 | 10/9/2006 | 10/9/2006 | A | FAIL |
Jack Frank
|
|
|
PAUL KLINDT - REINSPECTION; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy no access called
|
Final | 10/5/2006 | 10/6/2006 | 10/6/2006 | A | FAIL |
Mike Kinnear
|
|
|
PAUL KLINDT; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy nec400.8 used in cabinets.
|
Electrical Rough-In | 8/18/2006 | 8/18/2006 | 8/18/2006 | P | PASS |
Jack Frank
|
|
|
ceiling inspection Internet Inspection Request from: Tyler Bowen ok
|
Electrical Rough-In | 8/17/2006 | 8/17/2006 | 8/17/2006 | P | PART |
Jack Frank
|
|
|
PAUL UNDERGROUND AND CEILING COVER; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy u/g ok only corr. for ceiling, 300.11 support wires shall be from grid to structure, 330.30 (B)&(D2), 210.62 added show window outlet
|
Electrical Rough-In | 8/16/2006 | 8/17/2006 | 8/17/2006 | P | CANC |
Jack Frank
|
|
|
underground Internet Inspection Request from: Tyler Bowen Inspection cancelled from web by: Sean DeLacy
|
Electrical Rough-In | 8/16/2006 | 8/16/2006 | 8/16/2006 | P | FAIL |
Jack Frank
|
|
|
undergroud inpection on trenches for floor boxes; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen called notice posted fee due and not ready
|
Reinspection Fee (no hold) | 8/16/2006 | 8/16/2006 | 8/16/2006 | P | DONE |
Jack Frank
|
|
|
undergroud inpection on trenches for floor boxes; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen notice posted not ready fee due
|
Owner Supplied Equipment | | | 8/16/2006 | | |
|
|
|
|
Application received | | | 8/16/2006 | | DONE |
|
|
|
This permit was created on the web by Tyler Bowen
|