Final | 12/6/2006 | 12/7/2006 | 12/7/2006 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 12/6/2006 at 9:31:22 PM. Contact: ###-####. ok to final
|
Electrical Rough-In | 8/21/2006 | 8/21/2006 | 8/21/2006 | P | PASS |
Mike Kinnear
|
|
|
george; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok cover ri
|
Electrical Rough-In | 8/18/2006 | 8/18/2006 | 8/18/2006 | P | FAIL |
Bob Reichert
|
|
|
george ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr, left corr notice, nec 250.86 metal enclosures shall be grounded, 314.17(C) nm cable shall be stapled within 8" of boxes, 334.80 nm cable shall not be stapled on edge, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 210.52(A)(1) recpts shall be spaced such that no point along the floor line is over 6' from recpt outlet,BCC all make-up shall be done(back recpt), no violations shall be retained,verify room count-12 rooms minimum
|
Application received | | | 8/18/2006 | | |
|
|
|
|
Issue permit | | | 8/18/2006 | | DONE |
|
|
|
|