Temporary Service | 8/23/2006 | 8/23/2006 | 8/23/2006 | P | PASS |
Jack Frank
|
|
|
brian; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley t/s u/g new ok
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 8/23/2006 | | |
|
|
|
|
Temporary Service | 8/21/2006 | 8/22/2006 | 8/22/2006 | A | FAIL |
Jack Frank
|
|
|
brian; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley corr. called 312.5 needs conn for GEC, 250.53(G) drive grd rod flush, 406.8 needs inuse covers, 110.12(C) clean dirt from t/s and clean the busbars, needs address
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 8/21/2006 | | |
|
|
|
|
Application received | | | 8/21/2006 | | |
|
|
|
|
Override - Parcel Holds | | | 8/21/2006 | | |
|
|
|
|
Issue permit | | | 8/21/2006 | | DONE |
|
|
|
|