Final | 12/4/2006 | 12/4/2006 | 12/4/2006 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson ok to final
|
Final | 11/30/2006 | 11/30/2006 | 11/30/2006 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called left corr notice, nec 348.30(A) fmc shall be securely fastened within 12" of box (heater in mbr), 406.4(D) recpt faces shall be flush with or project from faceplate, 110.3(B) listed equipment shall be installed per mfgr instructions (tub access), BCC 4-05-33(A)(B) equip shall be listed by a nationally recognized testing lab (heater mbr closet)
|
Permanent Service | 8/26/2006 | 8/28/2006 | 8/28/2006 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson p/s o/h new ok
|
Rough-In Permanent Service | 8/23/2006 | 8/23/2006 | 8/23/2006 | A | PART |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson no p/s corr. needs 1/0 cu. 3/0 alum. to bond water 250.66, 250.64(C) shall not splice GEC, r/i ok survey for nail plates called
|
Application received | | | 8/23/2006 | | DONE |
|
|
|
This permit was created on the web by Therrin Robertson
|