Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberELE06-03137
StatusFinaled
Name TDR ELECTRIC
Site Address 911 N HOUSTON RD
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final12/4/200612/4/200612/4/2006PPASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson ok to final
Final11/30/200611/30/200611/30/2006PFAIL
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called left corr notice, nec 348.30(A) fmc shall be securely fastened within 12" of box (heater in mbr), 406.4(D) recpt faces shall be flush with or project from faceplate, 110.3(B) listed equipment shall be installed per mfgr instructions (tub access), BCC 4-05-33(A)(B) equip shall be listed by a nationally recognized testing lab (heater mbr closet)
Permanent Service8/26/20068/28/20068/28/2006APASS
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson
p/s o/h new ok
Rough-In Permanent Service8/23/20068/23/20068/23/2006APART
DetailsJack Frank
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson no p/s corr. needs 1/0 cu. 3/0 alum. to bond water 250.66, 250.64(C) shall not splice GEC,
r/i ok survey for nail plates called
Application received  8/23/2006 DONE
This permit was created on the web by Therrin Robertson