Rough-In Permanent Service | 8/25/2006 | 8/25/2006 | 8/25/2006 | P | FAIL |
Bob Reichert
|
|
|
gary; Phone #: ###-#### Internet Inspection Request from: Darla Downs called, left corr notice, nec 408.4 circuit directory shall be complete, concise , and explanatory for each circuit, 300.4(D) edge of nm cable shall be 1 1/4" from edge of framing member, 406.5,110.12(C) recpt faceplate shall cover opening at recpt and no broken parts shall be used, 334.30 nm cable shall be supported within 12" of flex under bench, 110.26 access and working space shall be provided at panel, BCC no violations shall be retained(open splices over bench),strap flex into panel Note: ok to cover u/g, looked at feeder from in house, it is ok
|
Rough-In Permanent Service | 8/24/2006 | 8/25/2006 | 8/25/2006 | A | CANC |
Jack Frank
|
|
|
gary; Phone #: ###-#### Internet Inspection Request from: Darla Downs canceled by contr.
|
Application received | | | 8/24/2006 | | |
|
|
|
|
Issue & PRINT permit | | | 8/24/2006 | | |
|
|
|
|