Second Notice ELE | 12/26/2006 | 12/26/2006 | 1/4/2007 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 12/12/2006 | 12/12/2006 | 12/26/2006 | | DONE |
Bob Reichert
|
|
|
|
Final | 12/12/2006 | 12/12/2006 | 12/12/2006 | P | PASS |
Bob Reichert
|
|
|
JOB COMPLETE FINAL INSPECTION KEY IS ABOVE METER. ; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called contr to add conduit straps, ok to final
|
Permanent Service | 11/22/2006 | 11/22/2006 | 11/22/2006 | P | PASS |
Bob Reichert
|
|
|
we are ready for a reinspection for perm. service. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH corr made, p/s u/g n ok
|
Permanent Service | 11/21/2006 | 11/22/2006 | 11/22/2006 | A | FAIL |
Jack Frank
|
|
|
WE ARE READY FOR PERM. SERVICE. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH corr. called 250.24(C) shall install neutral conductor from meter to p/s not grd wire, 250.30(A)(7) shall install GEC from xformer to u/g copper water not p/s panel bus, 210.5 (A B C ) ID 480/277 120/208 at all locations as code noted states, shall not use tie wraps for flex
|
Permanent Service | 11/15/2006 | 11/16/2006 | 11/16/2006 | A | FAIL |
Bob Reichert
|
|
|
PERMANENT SERVICE; Phone #: ###-#### x1 Internet Inspection Request from: BRIAN KEITH called contr to reverse ground and neutral in service panel
|
Rough-In Permanent Service | 10/18/2006 | 10/19/2006 | 10/19/2006 | A | CANC |
Jim Schmer
|
|
|
please inspect teh service so that idaho power can energize.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH chng to conference - needs fault current for service jms
|
Electrical Rough-In | 9/29/2006 | 9/29/2006 | 9/29/2006 | P | PART |
Jack Frank
|
|
|
need rough in on new building. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH corr. posted for damaged wiring done by concrete contr, shall repair or turn off power, called contr . will address problem, r/i for ceilings ok
|
Electrical Rough-In | 8/25/2006 | 8/28/2006 | 8/28/2006 | A | PART |
Jack Frank
|
|
|
need inspection on U/G for cover. thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH u/g inside of building and electrode ok only outside u/g shall be be 18" or under concrete called
|
Electrical Rough-In | 8/25/2006 | 8/25/2006 | 8/25/2006 | P | CANC |
Bob Reichert
|
|
|
need U/G inspection for cover. conduit will be installed by 1:30pm. if possible, please inspect after, thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH talked to elect, he asked to cancel said wanted shop to call for later inspection
|
Application received | | | 8/25/2006 | | DONE |
|
|
|
This permit was created on the web by BRIAN KEITH
|