Electrical Rough-In | 11/6/2006 | 11/7/2006 | 11/7/2006 | A | CANC |
Mike Kinnear
|
|
|
dennis ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith wrong permit #
|
Electrical Rough-In | 10/25/2006 | 10/25/2006 | 10/25/2006 | P | PASS |
Mike Kinnear
|
|
|
eugene Hm ###-####; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok cover ri
|
Electrical Rough-In | 10/19/2006 | 10/20/2006 | 10/20/2006 | P | NR |
Mike Kinnear
|
|
|
eugene; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles owner called & canc.
|
Electrical Rough-In | 9/25/2006 | 9/25/2006 | 9/25/2006 | P | FAIL |
Jack Frank
|
|
|
eugene; Phone #: ###-#### Internet Inspection Request from: Barbara corr. met owner part correction only job not ready 300.4 nail plates and 11/4", 210.52(A) 2ft wall 6ft 12ft, 314.16 box fill, 314.29 all boxes shall be accessible, 314.3&110.3(B) shall not use metallic fittings in non-metallic boxes, 110.12(A) seal all KOs, 250.148 grd all metal boxes, 200.42 calc circuits sq. ft and wet bar area, 310.16 shall not use #14 on 20 amp circuit, , BCC complete all wiring for r/i and all makeup shall be done COW
|
Conference | 8/29/2006 | 8/30/2006 | 8/30/2006 | A | PASS |
Mike Kinnear
|
|
|
gene ###-#### ok conf start up
|
Issue PAID IN FULL permit | | | 8/29/2006 | | DONE |
|
|
|
|
Application received | | | 8/29/2006 | | |
|
|
|
|