Electrical Rough-In | 12/19/2006 | 12/19/2006 | 12/19/2006 | P | PASS |
Jack Frank
|
|
|
Jack; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett ok corr. made
|
Electrical Rough-In | 12/15/2006 | 12/15/2006 | 12/15/2006 | P | FAIL |
Jack Frank
|
|
|
Jack; Phone #: ###-#### Internet Inspection Request from: Sherri Bennett corr T 300.5 u/g from house to new concrete shall be 18" deep called
|
Electrical Rough-In | 11/3/2006 | 11/3/2006 | 11/3/2006 | P | PASS |
Jack Frank
|
|
|
need inspection an the Equipotential Bond for the pool deck.; Phone #: ###-#### Internet Inspection Request from: Tollie Rogers ok
|
Electrical Rough-In | 10/10/2006 | 10/10/2006 | 10/10/2006 | P | FAIL |
Bob Reichert
|
|
|
tolly Note: lights for swimming pool; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles potting for lights ok, called contr, left corr notice, nec 680.10 there shall be no wiring within 5' of pool, 300.18 raceway system shall be installed completely before installing any wiring, 680.26(C) equipotential bond grid shall be installed, BCC no cover allowed without inspection-conduit or equipotential grid
|
Electrical Rough-In | 9/5/2006 | 9/6/2006 | 9/6/2006 | P | PASS |
Bob Reichert
|
|
|
Tollie, bonding for swimming pool; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt bond only ok
|
Application received | | | 9/5/2006 | | |
|
|
|
|
Issue permit | | | 9/5/2006 | | DONE |
|
|
|
|